Industrial, commercial and substations

     

WG.MT/MD8xx

Multifunction meters with load profile

The WG.MT/MD8xx electronic meter is for industrial customers and electric utilities.
It complies with IEC 61036 or IEC 60687 standards for active energy and complise with the IEC 61268 standard for reactive energy and VDEW requirements. The meter can be connected directly via CT or via CT and VT in 3-wire networks (MT851,MD851) and 4-wire networks (MT851).
The housing is made of self-extinguishing polycarbonate (IP51). Dimensions comply with the DIN 43857 standard.

Measured, calculated quantities and features

  • Active energy in two directions. Reactive energy in four quadrants
  • Maximum demand. Actual average demand. Cumulative maximum demand
  • Line voltages. Power factors. THD of line voltages (MT851 only)
  • Content of harmonics in line voltages (up to 15th - MT851 only)
  • Registration of energy and demand in up to 8 tariffs
  • 32 channel load profile recorder
  • Log book for different events registration
  • Up to 16 OptoMOS outputs. Up to 10 optically isolated inputs
  • IR optical port, RS232, RS485, CS (20mA) interfaces
  • MeterView software for local and remote reading and programming
  • Load contoller. Callback function on different events

Technical Data

Accuracy           KWh-meter...............................class 1(IEC 61036) or class 0.5S(IEC 60687)
                         Kvarh-meter.............................class 2(IEC 61268) or class 2,calibrated to 1%

  direct connected transformer operated
  class 2 or 1 class 1 or 0.5S(only MT851)
Basic current Ib 5A 1A
Maximum current Imax 120A 6A

Starting current          whole current meter..........0.004Ib
                                 transformer rated meter....0.002Ib
Reference voltage Ur.........................................3×220/380V,3×230/400V,3×240/415V
                                                                                3×58/100V,3×63/110V,3×100V,3×110V
Voltage range...................................................0.8Ur to 1.15Ur
Reference frequency ........................................50Hz ± 5%
Accuracy of quartz controlled RTC (at 25°C
)......≤±3 min/year (≤±6 ppm)
Memory capacity of load profile..........................84 days at 4 channels and 15-minute demand period
Number of auxiliary terminals.............................up to 34
Number of inputs...............................................up to 10
Number of outputs.............................................up to 16
Operating temperature range...............................-25°C to +60°C
Storing temperature range................................. -30°C to +70°C
Current circuit burden........................................<0.1VA /line
Voltage circuit burden........................................<3W/4VA
Relay ratings.....................................................25VA(100mA,275V)
Dielectric strength..............................................4kV,50Hz or 60Hz,1min
Impulse voltage..................................................6kV,1.2/50 μs
Short-circuit current............................................30Imax
Burst test..........................................................4kV(IEC 1000-4-4)
Dimensions........................................................327×177×90mm

 

OVERALL AND FIXING DIMENSIONS