ACU Sheet
   ACU Fact Sheet
   ACU Spec Sheet

ACU Fact Sheet

The ACU provides flexible multi-circuit monitoring for bus bars, feeders, switchgear, motors, generators and power distribution panels. Wire once to the ACU and see the same data at both local control panel displays and the control center(s).
The P2C™ Dual Core processor architecture makes it all possible.

Applications

Enhanced functionality compared with traditional, discrete meter installations

  • Economical metering for 3-phase feeders, switchgear and power distribution panels
  • Bi-directional power metering for co-generation monitoring
  • Up to 30 AC inputs per module for convenient monitoring of motor control centers. Daisy chain ACUs for even more circuits.
  • Multi-circuit design provides single connection point for easy wiring to field terminations
  • Distributed display panels don't need field wiring connected directly to them allowing easier, more flexible placement in control panels / switch boards
  • Integrated metering for display panel and SCADA interface so on-site staff and control center see the same data at the same time.
  • Integrates easily into existing GE D20, D25 or D400 SCADA systems.

Features

  • Up to 30 direct AC inputs in flexible configurations
  • 2 Optional DC inputs
  • Support for 1, 2, 2.5 & 3 element metering
  • Synchronized measurements to 100nS accuracy on all inputs with 1 PPS from GPS
  • Automatic tracking and adjustment for fundamental frequency
  • Revenue class metering: ±0.5% accuracy
  • Frequency accuracy: ±0.01Hz accuracy
  • Up to 31st Harmonic and THD calculations
  • 64 samples per cycle
  • Individual Display Panels for each circuit
  • Pushbutton on Display Panel to advance display values through measurement groups
  • Optional Web server support to view data via Internet Brower
  • GPS time synchronization, NMEA 0183 Interface Standard compliant

Communications Options

  • D20 HDLC Link
  • RS-232/485 up to 115kbaud
  • 10/100 Ethernet
  • DNP3.0
  • IEC 60870-5-101/104
  • Modbus


ACU Spec Sheet

AC Inputs
up to 30 PT/CTs in flexible configurations
±0.2% accuracy on sampled values
±0.5% accuracy on power calculations
±0.01Hz accuracy on frequency measurement
THD up to 31st harmonic
64 samples per cycle
Automatic fundamental frequency adjustments
Sample and hold of all 30 inputs eliminates effects of phase angle and magnitude changes during the sampling cycle assuring accurate power calculations.

DC Inputs
+/-5Vdc
±1mA, ±20mA, 4-20mA
Accuracy: 0.2% of full scale @ 25C
16-bit resolution

Communication Ports
2 RS-232 or RS-485 ports
1 RS-485 port
1 10/100aseT Ethernet port
1 D20 HDLC port
1 RS-232 maintenance port

Field Terminations
PT/CT: #10 AWG barrier
DC Input: #12 AWG compression
Earth ground: #12 AWG compression
Serial Ports: DB9 Female
Ethernet: RJ45

Memory Model
Flash ROM: 8MB NVRAM: 2MB
SDRAM: 32MB  

Power Supply
20-60Vdc input
1500Vac isolation
Reverse polarity protection
Input fuse for protection
15W maximum input supply

Dimensions
Up to 15 PT/CT: 19" (L) x 8.75" (H)
Up to 30 PT/CT: 19" (L) x 10.46" (H)
LED Display Panel: 4.2" x 4.2" x 1"

Environmental
Operational Temperature: -25° to +55°C
Storage Temperature: -40° to +85°C
Humidity: 93% non-condensing at 55°C